About the product
- Top class measurement and accuracy
- Automatic test sequence
- Bi-polar pre-location for the elimination of external influences
- Detection and indication of wrong connections
- Only one high voltage connection cable
- Completely independent of the parameters of auxiliary lines
- Easy Go operating system
HVB10 is a highly accurate high voltage (HV) bridge designed to locate cable and sheath faults, perform sheath testing, and pinpoint sheath faults. It is particularly suited for long HV cables.
With its top resolution, intermittent fault detection function, and load adaptation for faster cable charging, the HVB10 is an indispensable tool for all utilities that want to reduce downtime and facilitate the repair of power in, for example, pilot and communication cables.
The HVB10 has two different methods for fault location:
- The standard mode: This provides good results for typical sheath faults faults with fault resistances of up to some hundreds of kilo Ohms and shield cross sections in the range of 25 to 50 mm2. This measurement is typically done in app 30 seconds
- The high accuracy mode: This takes approximately 1 minute for the algorithm to complete, but will use the full potential of the measuring and control circuits of the instrument. Thus, it is ideally suited for pre-locating difficult, high-resistive faults (e.g., in the inner insulation of PILC cables). An intermittent fault detection algorithm is applied to gain a result under even worse conditions with sparking faults.
Technical specifications
- Power source
- Battery
- Test type
- Sheath fault location
More details available on the product data sheet
Product documents
Software and firmware updates
EasyProt
Version for use with:
- MFM10
- ETray
- Easytester 10/20kV
- NIM 1000
- VLF Sinus 28/30/34/51/54
- VLF Sinus 45/62 (TDM 45/62-P)
Installation instructions:
- Download the zip archive.
- Open the zip archive.
- Copy the EasyProt62 folder to the desired installation folder.
- Open the installation folder.
- Double-click on EasyPro.exe, if you want to import log files from any aforementioned product other than VLF Sinus 62.
otherwise....
- Double-click on EasyProt_62.exe, if you want to import VLF Sinus 62 log files.