More than 40 years of experience
Ensure the safe and efficient distribution of power with our tried and tested solutions, supported by our extended industry experience and expertise.
Circuit breakers must operate instantly and correctly to protect your power system. Megger’s testing solutions help you measure opening time, contact speed, and coil current, giving you the insight needed to confirm operation, detect emerging issues, and maintain protection system integrity.
Perform circuit breaker maintenance safely with Megger’s advanced testing solutions. Purpose-built technologies and proven test methods help you verify breaker condition while maintaining safe working practices and protecting personnel and critical equipment.
Breaker failures can lead to extended outages and equipment damage. Megger’s diagnostic tools help engineers detect mechanical wear, contact degradation, and performance issues early, ensuring reliable protection and reducing the risk of unexpected failure.
Use diagnostic data to support condition-based maintenance and identify breakers at risk of failure. Megger’s testing solutions give you the insight needed to plan maintenance, optimise capital investment, and make informed asset management decisions.
There are many reasons for testing circuit breakers. Some of the most important are to ensure they:
The two predominant standards are:
NETA also has acceptance testing (NETA ATS) and maintenance testing (NETA MTS) specifications that cover a broad range of electrical equipment, including circuit breakers.
First, make a reference measurement (footprint) of the circuit breaker when it is new and use this to compare future tests. Use the default settings for speed calculation points. Alternatively, if the circuit breaker is older, check to see if several breakers of the same type are available to test. Compare results with other circuit breakers of the same kind. These should be from the same manufacturer and model type, not just the same rated voltage and current. Also, you can make some checks within the test. For most breakers, all three phases should be within 1 to 2 ms of each other, but occasionally a 3 to 5 ms difference may occur for some older breakers. When the breaker has multiple breaks per phase, the difference between contacts in the same phase should be approximately 2 ms or less. On modern circuit breakers, the trip times should be between 20 to 45 ms, with close times taking longer but generally less than 60 ms.
Testing should be done at various stages in the life of a circuit breaker, including:
The manufacturer typically provides a list of the parameters you should check and the range of values you should expect. The list can vary by breaker design, but if none is provided, at a minimum, you should measure the following:
Contact us to talk about your unique circuit breaker testing needs. One of our experts will reach out to you to offer more information and assistance.
Take a deeper dive into circuit breaker testing through our comprehensive guides.
Understand what it takes to keep circuit breakers at peak performance.
Take decisive action during commissioning, maintenance, or troubleshooting.
First trip analysis anticipates faults before they become critical.
See the challenges of ground fault testing using primary injection.
Learn how to select the right instrument and how to interpret the results.
Get the lowdown on a more efficient alternative to short circuit testing.