PD APPLICATIONS - POWER, DISTRIBUTION & INSTRUMENT TRANSFORMERS
On- and off-line testing
Performing partial discharge (PD) testing on power, distribution, or instrument transformers in the field presents significant challenges for service engineers or commissioning teams. These on-site assessments can be performed on-line, meaning the transformer is connected to the grid and energised, or performed while the transformer is off-line, meaning it is powered by a mobile power system. Both methods have advantages and disadvantages, as listed below:
On-line PD testing advantages:
- Transformer is under load condition (full current): Testing occurs while the transformer is operating at its usual load, providing real-world insights.
- Rated voltage and frequency: Measurements reflect actual operating conditions.
- Up-to-date insights into insulation system condition: Continuous monitoring ensures real-time data on insulation health.
- Early detection of insulation degradation or potential faults: Identifies issues before they lead to failures, reducing downtime and maintenance costs.
- Continuous operation of the asset: Allows the system to remain operational during testing.
- Integration with condition monitoring systems: Enables comprehensive analysis of equipment health by combining PD data with other monitoring information.
On-line PD testing limitations:
- No variable voltage and frequency: Testing is limited to the operating conditions of the transformer, eliminating access to additional insights.
- Almost no access (or limited access) to the transformer tank: Restricted ability for further inspection.
- Difficult for fault investigations
- Cannot distinguish PD inception voltage (PDIV) and extinction voltage (PDEV): These critical parameters cannot be separately identified.
- Requires special equipment and expertise
- Highly affected by electrical noise: External electrical interference can impact measurement accuracy.
Off-line PD testing advantages:
- Full variable voltage and switchable frequencies
- More detailed analysis of partial discharge activity
- Reduced electrical noise: Asset disconnection from the grid minimizes interference.
- Manipulation of the power supply: Independent from grid conditions, allowing tailored testing scenarios.
- Concurrent testing capabilities: Ability to perform other diagnostic tests, such as insulation resistance, tan delta (power factor), and winding resistance.
- Cost savings and the portability of power supplies for on-site settings
Off-line PD testing limitations:
- May not capture transient or intermittent partial discharge events: These events occur during normal operation and might be missed during offline testing.
- Requires downtime: The asset must be taken out of service, impacting operational schedules.
- Lacks real-time insights: Does not provide ongoing information about the insulation system’s condition.
- Potentially undetected faults: Issues might go unnoticed between maintenance periods, leading to possible risks.
Typical Packages
1) Set for power transformer onsite testing:
- 1 x ICMsystem (4 or 7 channels)
- 1 x Extension board for parallel spectrum analysis
- 1 x GPIB interface
- 1 x Software ICMsystem
- 1 x Laptop computer
- 1 x Impulse calibrator CAL1D or CAL1B
- 3 x Preamplifier RPA1
- 3 x Preamplifier RPA1L
- 3 x Quadrupole CIL4M/V0m5/2m0
- 3 x Quadrupole CIL5M/V4m0
- 3 x Coupling capacitor CC35B/V
- 1 x HF current transformer CT100
- 1 x Oscilloscope
- 3 x Acoustic sensors AS75I
- 3 x Magnetic holder for AS75I (SFX2)
- 1 x Set of cables
- 1 x Transportation case