PD Applications - Rotating Machines

Testing laboratory

The quality of the stator winding insulation system should be verified according to the following brief description of the test procedure:

The test requires an AC power source capable of supplying a partial discharge (PD)-free 50 or 60 Hz variable voltage up to at least the rated line-to-ground voltage of the insulation system under test. PD measurements are then taken in voltage steps up to the rated line-to-ground voltage of the insulation system to measure the discharge inception voltage (DIV) and the discharge extinction voltage (DEV). The maximum PD magnitude at line-to-ground voltage should be less than 50 pC.

References:

IEEE 268-2000
"IEEE Recommended Practice for Measurement of Power Factor Tip-Up of Electric Machinery Stator Coil Insulation"

 

EN50209-1998
"Test of insulation of bars and coils of high-voltage machines"

 

IEC 60894-1987
"Guide for a test procedure for the measurement of loss tangent of coils and bars for machine windings"

Connection Diagram with ICMflex

ICMflex connected to a single stator bar under test

Typical Packages:

1) Advanced PD measurement system

2) Standard PD test system

3) Combined PD and TD measurement equipment