Transformer insulation testing

Assessing high voltage substation equipment at 1 Hz

7 July 2023
-
This article provides a clear demonstration of the benefit of measuring insulation DF at LF (50 or 60 Hz) and at 1 Hz.

It is common practice to evaluate the average insulation condition of high voltage (HV) substation equipment in the field by measuring dielectric losses. 

This practice involves applying an AC signal to an insulation system at a frequency close to the line-frequency (60 or 50 Hz) and measuring the current and the angle between current and applied voltage to determine the insulation dissipation factor (tan delta) or power factor.

Line-frequency (LF) insulation dissipation factor (DF) or power factor (PF) depends on the frequency of the applied signal, the dielectric properties of the insulation material, the insulation temperature, and the geometrical design, as well as aging and contamination that might be present within the insulating medium.

Field experience suggests that tables of factors for temperature correction do not reflect the true thermal behaviour of the insulation system and, consequently, a DF or PF trend analysis may be misleading due to incorrectly temperature-compensated test results. 

Throughout the service life of an electrical asset, line-frequency dissipation factor (LF DF) may stay the same, may increase or sometimes may even decrease and the reason for these changes is not always clear.

Research carried out by the authors shows that even an apparently ‘good’ line-frequency DF is not always ‘good’, and that to reliably determine the condition of the insulation system, assessment of the insulation should also consider an additional DF value obtained at another, very specific, frequency.

This article provides a clear demonstration of the benefit of measuring insulation DF at LF (50 or 60 Hz) and at 1 Hz

This simple combination of procedures carried out at the same time and with the same test instrument provides a more reliable and more efficient way to evaluate the condition of critical high voltage substation equipment, including power transformers, bushings, and instrument transformers.

 

Theoretical background

 

Dielectric response in the frequency domain

 

Non-invasive and non-destructive methods for determining the dielectric characteristics of insulation systems have evolved significantly in the last two decades

The methods typically involve applying a sinusoidal signal to the insulation system. This is not done to stress the insulation but to measure its dielectric properties: capacitance, dissipation factor (DF), complex permittivity, and conductivity

The ratio of imaginary to real components of the complex permittivity is the insulation DF (tan delta, δ).

 

 

1hz_ETarticle_Jul_Equ1.jpeg

 

Equation 1

 

Physical and/or chemical properties of organic and inorganic materials can change due to aging and due to thermal, chemical, electrical, or mechanical stress. 

A non-invasive and non-destructive method to trend these changes in insulating materials is the measurement of dielectric losses performed over wide ranges of frequencies or temperatures. 

The dielectric frequency response provides an instantaneous image of the condition of the insulation system, and it therefore allows on-site assessment and comparison against historical values – but only if accurate temperature correction is carried out in line with the Arrhenius equation (Equation 2), which defines the relationship between frequency and temperature.

 

1hz_ETarticle_Jul_Eq2.jpeg

 

Equation 2

 

Where Ea is the activation energy of the insulation material in eV, kB is the Boltzmann constant (8.617 x 10-5 eV/K), and T is the Kelvin temperature of the object. 

Activation energies are in the range of 0.70 - 1.18 eV for oil impregnated cellulose insulations. 

 

1hz_ETarticle_Jul_Fig1.jpeg
Figure 1: Dielectric response of OIP insulation (new oil and paper with 2 % moisture) tested from 0 °C to 40 °C

 

The Arrhenius equation allows normalisation of the dielectric response to a reference temperature, which 
is typically 20 °C

This approach is known as individual temperature correction (ITC). 

The effect of temperature on an oil-impregnated paper (OIP) sample is shown in Figure 1.

 

Line-frequency dissipation factor (LF DF)

 

The measured LF DF value by itself does not provide much information unless it is properly corrected to 20 °C. 

In a power or distribution transformer, the interwinding insulation, as well as the winding-to-ground insulation systems, are tested using an applied voltage of 10 kV (or below rated voltage of the winding under test) at line frequency. 

The resulting normalised values are subject to at least one of three typical evaluations: 

  • comparative analysis
  • trending analysis
  • acceptance within limits established by international standards

It is not only the LF DF value that is of importance but also the capacitance value

Field experience has, however, shown that HV equipment may fail even after an LF DF test with apparently acceptable results.

Reasons for not detecting insulation problems with LF DF are related to the temperature dependence of DF and the very marginal effect of emerging contaminants at LF. 

Carrying out the test at an additional frequency is a practical approach to improving the assessment by providing two measurement points within the dielectric response spectrum.

 

Dissipation factor at 1 Hz

 

More than 25 years of information that was obtained using full spectrum (1 mHz to 1 kHz) dielectric frequency response (DFR) in the field to assess the condition of power transformers has been thoroughly analysed at various frequencies.

As can be seen in Figure 1, at LF (60 Hz) the variation of DF as a function of temperature is very small compared to the variation observed at 1 Hz. 

The differences at LF are quite difficult to observe, particularly for a specimen in very good condition, with no contamination, less than 0.5 % moisture in the solid insulation, and very low oil conductivity.

Here is the where the importance of the 1 Hz test comes in

As shown in Figure 1, the higher frequency region of the response represents a relatively linear low-loss system. At a resonant frequency ωr, the dielectric response transitions into a lower frequency region represented by higher losses and greater dispersion of the dielectric response. 

The resonant frequency will shift to higher values when temperature increases and lower values when temperature decreases, as shown in Figure 2. 

It is important to know to what degree a change in test temperature has caused the resonant frequency to shift because changes in the vertical or horizontal axis imply a change in the dielectric condition. 

Therefore, to eliminate temperature as a factor for an observed change, the entire response must be properly normalised to 20 °C every time a measurement is made at a non-20 °C temperature.

 

1hz_ETarticle_Jul_Fig2.jpeg
Figure 2: Resonant frequency shift in a dielectric response at different temperatures

 

Field applications

 

Bushings

 

Condenser-type bushings, more commonly known as capacitance graded bushings, have been in service for 
a long time and have been tested in many ways. 

The dielectric response of a bushing in the time or frequency domain is mainly dominated by its construction, the temperature during the test, and the properties of the materials. 

In most HV and EHV (extra high voltage) bushings, a geometric design for the main insulation replicating a graded capacitor is commonly used. Oil-impregnated paper (OIP) insulation is used in the vast majority of field-installed bushings, wherein the liquid insulation is mineral oil, and the solid insulation is typically kraft paper with a 55 °C rise thermal rating. 

Both materials possess well known and excellent mechanical and dielectric characteristics. Other common types of HV bushings are resin-impregnated paper (RIP) and resin-impregnated synthetic (RIS).

Because the failure of bushings has a large impact on transformers, the condition assessment of HV bushings has been extensively investigated and CIGRE has recently published a very detailed document describing the reliability of HV and EHV bushings [1]. 

Several of the methods used for testing HV bushings are sometimes ineffective and the results inconclusive. Off-line testing of capacitance and dissipation factor is generally carried out at line frequency as part of acceptance, commissioning, routine testing and troubleshooting, or after corrective maintenance work. 

Changes in capacitance may be indicative of a short between capacitive layers in C1 (the main core insulation) and changes in dissipation factor (or power factor or tan delta) may indicate insulation degradation and/or contamination. 

Contamination of the insulation due to overheating or excessive generation of partial discharge (PD) and consequently of PD by-products such as X-wax, has a clear influence on dielectric response [2].

As presented in [3], the influence of contamination on dielectric response may be significantly more pronounced at non-line frequencies than at LF

Assuming accurate temperature correction using the ITC algorithm, the authors suggest that the insulation condition of OIP bushings can be assessed as shown in Table 1.

 

Table 1: OIP bushings assessment for 1 Hz DF at 20 °C

 

Transformers

 

The dielectric response of power and distribution transformers over a wide range of frequencies has been investigated for the last 25 years

In the last decade, several accelerated aging experiments have been carried out and published, particularly for distribution transformers [4]. 

Aging of distribution transformers has been shown to have very little effect on the LF DF value, but much greater changes were observed at lower frequencies, specifically at 1 Hz.

 

1hz_ETarticle_Jul_Fig3.jpeg

 

Assuming accurate temperature correction using the ITC algorithm, the authors suggest assessing the insulation condition of OIP transformers as shown in Table 2.

Table 2: OIP Transformers assessment for 1 Hz DF at 20 °C

 

Instrument transformers (CTs, VTs, and CVTs)

 

Instrument transformers monitor power flow and serve several purposes, including metering (for revenue purposes), protection, and control. 

For current transformers (CTs), the insulation system is like that of HV bushings, and an assessment is made on the dissipation factor of the overall insulation. 

Voltage transformers (VTs) and capacitive voltage transformers (CVTs) also have something in common with CTs and HV bushings. Instrument transformers usually have insulation consisting of kraft paper and mineral oil, and the volume of paper insulation is dominant. 

The measured capacitance of instrument transformers and HV bushings is typically less than 800 pF. Therefore, to make measurements at low frequencies, an HV source may be required to offset the negative influence of EMI and to increase the signal-to-noise ratio (SNR).

Dielectric frequency response (DFR) testing has been used to monitor the dry-out process of CTs and CVTs in the factory [5], down to levels below 1 % moisture in the solid insulation.

 For CTs, DF at 1 Hz and LF should reach values below 0.3 % at 20 °C. Similar values apply to CVTs. It is shown in [6] that the insulation condition of HV and EHV CTs can be readily evaluated in the field by using LF DF values in conjunction with 1 Hz DF values. 

The authors suggest that the assessments shown in Table 1 for OIP bushings can also be applied to instrument transformers.

 

Field experience

 

Commissioning new 69 kV RIP bushings

 

Commissioning tests conducted in the field in early 2021 involved dielectric assessment of new 69 kV RIP bushings. Nameplate data is provided in Table 3.

Table 3: New RIP bushings C1 nameplate information

 

An LF DF test was performed at 3 °C. 

The curves provided in section 5.2.2.2 of [1] were used for LF DF temperature correction.

Table 4: Tertiary winding new RIP “Y” bushings LF DF results

 

The results, as presented in Table 4, fall within the ‘acceptable’ limits prescribed in CIGRE guidelines [1] for new RIP bushings – (see Table 5).

Table 5: Limiting values LF DF at 20 °C [2]

 

During commissioning, a Megger DELTA 4310A dissipation factor test set was used for DF tests at LF and at 1 Hz

The application software corrected the % DF values from 3 °C to 20 °C using the individual temperature correction (ITC) algorithm. 

The results are shown in Table 6.

Table 6: RIP LF and 1 Hz DF values corrected by ITC

 

The results in Table 6 show a significant difference in the temperature correction of the 60 Hz % DF results for bushing Y2 compared with bushings Y1 and Y3: the correction decreases the value for Y2 but increases the values for Y1 and Y3. 

With a good bushing, temperature correction would be expected to decrease the value obtained at 3 ºC to yield its 20 ºC equivalent value, as was the case for Y2. 

Tests conducted on a sister transformer did, in fact, confirm that temperature correction decreased the values for all three bushings, as expected.

After applying ITC to the results, the Y1 and Y3 bushing LF DF values at 20 °C are above the acceptance limit (> 2 times nameplate DF value according to IEEE guidelines). These two bushings were therefore assessed as ‘investigate’. 

The large difference observed between the corrected DF values at 1 Hz for bushings Y1 and Y3, which are more than five times higher than the value for Y2, is clear indication of an insulation issue.

When the results were discussed with the commissioning team, it was reported that the Y bushings had been improperly seated during transport and water had been observed in the plastic wrapped around them. They asked for action to be taken to remedy the problem and the transformer manufacturer decided to have the bushings returned to a maintenance facility for inspection, repair, and drying out. 

To confirm improvement, when the bushings were returned to the site (approximately six weeks after the original tests) they were retested at 5 °C. The results are shown in Table 7.

Table 7:  Reconditioned RIP bushings – LF DF and 1 Hz DF results

 

Drying out improved Y1 and Y3, resulting in all Y bushings coming within 0.02 % of nameplate values. These tests allowed the Y bushings to be approved for use in this new transformer.

 

New transformer (2019) – 16 MVA 138 kV – elevated moisture

 

The presence of moisture in power and distribution transformers has a negligible effect on the LF DF value obtained at 20 °C. It is only when the moisture concentration is typically greater than 2 % that significant changes are seen in this value.

A new transformer was tested after assembly and before energisation. 

Dryness of the solid insulation is critical to ensure the longevity of the transformer and reliability during operation. 

Figure 4 shows the influence of temperature and moisture on the service life of a typical transformer [7], while Table 8 shows the LF DF and 1 Hz DF results obtained for the new transformer under test. 

Table 8:  Interwinding insulation DF results

 

The LF DF values corrected to 20 °C using ITC are excellent. Nevertheless, reference to Table 2 will show that the 1 Hz temperature-corrected DF ITC corresponds to a ‘good’ transformer rather than a ‘new’ transformer as expected.

Full-spectrum DFR confirmed the presence of 1.6 % moisture in the solid insulation, and the need to dry out the unit before energisation. After seeing the LF,  1 Hz, and DFR test results, the customer requested a complete oil analysis. 

The physical-chemical analysis of the oil confirmed the presence of moisture (see Table 9) exceeding the acceptance level of 10 ppm suggested in IEEE Std. C57.106 Table 2. 

Table 9: ASTM D1533 results

 

EHV Capacitive voltage transformer (CVT) – 765 kV

 

Instrument transformers and, more specifically, CVTs have no monitoring instrumentation mounted on them to detect any changes in the insulation condition. 

Oil sampling is only an option during planned outages, and it is not a simple process. EHV CVTs typically have no oil sampling ports available for each capacitive section (stack) and therefore accurate assessment of the insulation condition through non-invasive and non-destructive methods is extremely important for utility operators.

In this example, during planned maintenance on an A-phase CVT, a small oil stain was seen on the surface of the adjacent B-phase CVT C1-1 stack. 

As shown in Table 10, LF DF results are higher than the results for sister stacks, but these results on their own are not necessarily enough to take decisive action.

Figure 4: Influence of temperature and moisture on solid insulation lifetime [8]

 

Table 10: LF and 1 Hz DF values obtained from B-phase EHV CVT

 

Once again, however, 1 Hz DF results confirm that the C1-1 insulation is degrading. Such degradation may result in catastrophic failure affecting adjacent equipment, the environment, and personnel working in the area. The unit was removed from service for investigation. Upon disassembly, a puncture was found in the C1-1 stack, which was allowing the oil to leak.

 

Conclusions and recommendations

 

Insulation condition is the most important factor in determining the life expectancy of a transformer. The ability to make early and conclusive decisions about insulation condition is critical for the reliability of HV electrical power systems. 

The use of LF DF together with 1 Hz DF results, all properly corrected to 20 °C using the Individual Temperature Correction (ITC) algorithm, provides high sensitivity to changes in the insulation system of HV equipment.

The combined analysis of LF DF plus 1 Hz DF (ITC corrected) allows quantitative condition assessment of new and service-aged transformers and bushings as suggested by the authors in Tables 1 and 2. 

The 1 Hz DF with ITC assessment does not require trend analysis, although it is also possible to trend the results.

Traditional line frequency measurements and reference temperature correction tables based on averages may be misleading and using them may sometimes make it impossible to carry out reliable assessments in both hot and cold environments.

Supplementing traditional 10 kV LF DF measurements with 1 Hz DF (ITC corrected) testing marginally increases the overall time required for testing – usually by less than one minute – but it helps to extend the life of HV and EHV assets by providing reliable support for sound technical and financial decisions, or for future investigations and definitive analyses using DFR technology.

 

Authors: 

Dr Diego Robalino

Vince Oppedisano

Ken Petroff

 

REFERENCES

[1]    CIGRE TB 755, ‘Transformer bushing reliability’, CIGRE WG A2-43, 2019

[2]    Güner I., Robalino D. M., Werelius P., ‘HV and EHV bushing condition assessment – field experience’, Proceedings of the 2016 CIGRE-IEC Colloquium, Montreal, Canada, 2016

[3]    Robalino D., Alvarez R., ‘Advances of Dielectric Frequency Response Testing for HV OIP Bushings’, Proceedings of the CIGRE Session 48, paper A2-206, Paris 2020x

[4]    Robalino D. M., Breazeal R… C., ‘Evaluation of Distribution Class Transformers Using Narrowband Dielectric Frequency Response Mea-surements’. Proceedings of the IEEE 2020 Electrical Insulation Conference, 2020

[5]    Perrier C., Roman Z., Kieffel Y., ‘Monitoring of active part drying for instrument transformers by dielectric measurements’, Proceedings of the CIGRE Session 48, paper D1-122, Paris 2020

[6]    Robalino D., Güner I.,’HV and EHV current transformer dielectric condition assessment and root cause analysis’, Proceedings of the 2019 CIGRE Canada Conference, paper CIGRE-133, Montreal, 2019

[7]    CIGRE TB 445, ‘Guide for Transformer Maintenance’, CIGRE WG A2-34, 2011