SPI4000 smart primary injection test system
Space-efficient power for testing even in the tightest quarters
The SPI4000, the smallest primary injection test system in its class, packs a punch with its compact design. It not only fits seamlessly into tight testing environments but can also slip through standard door openings, ensuring testing power wherever you need it.
High current capacity
With a maximum frame size of 4000 Amps, the SPI4000 excels in providing substantial current levels for precise testing of circuit breakers and related equipment, ensuring it meets the demands of industrial and electrical applications.
Exceptional mobility, guaranteeing your testing equipment is ready and onsite when you require it
Weighing only 514 lbs, the SPI4000 is remarkably lightweight for a high current primary injection test system. Its portability not only simplifies transportation but also reduces shipping costs, making it an economical choice for users requiring mobility and ease of relocation
Effortless precision with automatic zero crossing
One of the unique features of the SPI4000 is the ability to automatically adjust the output firing angle at the current zero crossing for every load. This eliminates DC offset for all circuit breaker types and removes the need for manual adjustment of firing angles, streamlining the testing process and ensuring accuracy across different loads and circuit breakers.
About the product
The SPI4000 is a high current primary injection test system with the flexibility to test, via primary injection, a wide variety of devices, including low voltage power circuit breakers, moulded-case circuit breakers equipped with thermal magnetic or electronic trip devices, overcurrent relays, and thermal relays. Designed to accommodate circuit breakers with ratings of up to 4000 Amps frame size, the SPI4000 fully complies with NEMA AB-4 test guidelines.
The SPI system is the first high current test system that allows you to type in a predetermined current amplitude and will then generate and regulate the requested high current without preheating the test sample by pulsing the output current at high amplitudes. Additionally, the SPI system has the unique ability to turn on at the current zero crossing every time for any load by automatically adjusting the output firing angle. This eliminates DC offset for all circuit breaker types and eliminates the need for you to determine and manually adjust the firing angle for various loads and circuit breakers.
FAQ / Frequently Asked Questions
The SPI4000 can be lifted with a forklift using the under carriage of the unit. Additionally, straps or chains could be attached to the unit’s lifting eyes. For ease of loading in vans or trailers, there are two eye hooks on the side that allow the SPI4000 to be hoisted up a ramp.
We offer two models. One model features wheels similar to the DDA units, which are solid wheels. These wheels are great for concrete floors and will not go flat. The second model is equipped with pneumatic wheels, which are recommended for navigating rough terrain.
The SPI4000 comes with an adaptor plate that allows existing DDA stabs to work with the unit. It also has a connection point for flexible stabs.
The SPI4000 is autosensing and will detect and operate on 240 V. You don’t need to change taps or anything else as the unit will autosense input voltage.
We recommend that you use a 150 kVA or larger generator with the SPI4000. Nevertheless, the SPI4000 can generate sufficient current to test most breakers, even with a generator as small as 75 kVA.
The SPI4000 was tested on generators of various sizes and exhibited no operating issues. When operating on generator power, the limiting factor for output current will be the generator’s output voltage. During high current tests, the generator’s voltage regulator will respond to voltage fluctuations in an effort to maintain the output voltage. Any reduction in the SPI’s output capacity will be proportionate to the extent of the voltage drop. For example, if the generator’s voltage experiences a 10 % drop, this will result in an approximate 10 % reduction in the output.
The SPI4000 has been tested with several different 4000-amp and 3200- amp breakers using the CBS2 or CBS3 stabs, and in all cases the unit was able to deliver 40 000 amps.
Further reading and webinars
Troubleshooting
The SPI4000 sends output pulses that are 130 % of the maximum trip time on the curve. When testing with a generic breaker form, make sure the maximum trip time is correctly filled out. If necessary, the advanced setting will enable you to configure a longer pulse duration.
To perform long-time pickup tests, the SPI finds 80 % of the pickup current, then gradually increases the current. You are then prompted to press the “Simulate Breaker Trip” button on the top right of the screen when pickup occurs, as indicated by the light on the breaker’s trip unit which will be blinking or remaining solid. Next, the SPI begins to decrease the current, and you should press the button again when the pickup drops out, indicated by the pickup light turning off on the trip unit. Finally, the SPI increases the current once more, this time at half the speed of the initial increment. You should press the button a third time as soon as the pickup indicator/light comes on again. This process enhances the accuracy of the recorded pickup current. If the long-time pickup is not recording accurately, the user can select “advanced settings” before the test to configure the ramp. The time can be slowed down if it’s occurring too quickly for you, enabling you to avoid inaccuracies.
For proper operation, the unit must be connected to earth/ground (hereafter referred to as ground). The output will not be energised unless the unit detects a secure grounding connection. Please ensure that there is a solid and secure connection to ground.
During an instantaneous pickup test, the SPI will first ramp up to 80 % of the requested current and then continue to ramp up to the requested current. If 80 % of the requested current trips the breaker, then the “Lower Starting Current” message will appear. This indicates that the starting current was too high and caused the breaker to trip before it could reach the requested current.
There are several ways to address this issue. You can lower the requested current to ensure the starting current is below the breaker’s trip threshold. Alternatively, you can adjust the settings to reduce the percentage of requested current from 80 % to 60 % or 70 %. Additionally, it’s worth checking the short-time settings on the breaker’s trip unit, as unadjusted settings can also cause the breaker to trip prematurely before reaching the instantaneous pickup current.
Two primary factors significantly influence the output current achievable from any primary injection test set.
Input voltage – The output magnitude is proportional to the input voltage. If you have a weak source or high resistance input leads, these factors can result in a reduction in output power.
Connections to the test specimen – Connections to the test specimen have a considerable effect on the current magnitude the instrument can deliver. Connection through the breaker stabs is crucial and can introduce resistance. Ensure a proper connection is established through the stabs and the proper bus size is being used. If the stabs are loose in the finger clusters of the breaker, it might be possible to add bus spacers between the test set stab and the breaker connection to further tighten the connection. If using flexible stabs, the output current will be reduced as this type of conductor has a higher resistance when compared to solid connections. For example, to push 30 000 amps through a breaker at 10 V, the output circuit resistance must be 330 micro-ohms or below. Any extra bus or a loose connection will add resistance and quickly limit the amount of current the unit can deliver.
Interpreting test results
Proper primary injection testing of low voltage circuit breakers (LVCB) will confirm that they trip at the correct times and can properly isolate a fault. A coordination study is performed, and parameters are set to minimise the amount of interruption to other equipment. The characteristics of the circuit breakers are presented in the form of trip curves, and each circuit breaker will have a unique trip curve published by the manufacturer. The trip curves will have bands, or limits, that show how long it takes for the circuit breaker to trip when a certain amount of current is applied; the current is typically presented in multiples of the rated current. As long as the circuit breaker trips within the specified band, it operates correctly. You may perform up to four primary injection test types to verify that the LVCB is working correctly: a long time test, short time test, instantaneous test, and earth/ground fault test. The long, short, and ground fault tests all have a delay component. In contrast, the instantaneous test trips the circuit breaker immediately.
The long time test is a test of the overload function and requires two settings. The first setting is the pickup, which determines the load current level that is tolerable before an overload condition occurs. The second setting is the time delay that determines how long the overload condition is acceptable. Systems are generally designed to handle overload conditions for a short time. Still, damage will occur if the overload persists for too long. You typically perform a long time test at 3 times the rated current.
The short time test is also an overload test with a pickup time like the long time test but has a shorter duration with a higher current. Typical currents are at 6 times the rated current. A short time setting on the breaker is used to allow high current loads for a short duration, for example, a motor starting.
The instantaneous trip conditions test the breaker under fault conditions. Therefore, there is no intentional time delay built in, and the breaker should trip within milliseconds. If the circuit breaker fails to trip and clear the fault, this may result in damage to equipment or personnel. Additionally, an upstream breaker may need to clear the fault, resulting in other electrical system components unrelated to the fault being shut down. An instantaneous trip is typically tested using 8 to 12 times the rated current.
An earth/ground fault trip in the circuit breaker occurs when higher-than-normal currents flow through the ground path. Like the long time and short time functions, the ground fault has both a pickup current and a delay time. Both can be adjusted to fit the coordination study. There is typically a maximum delay that is permitted from ground fault conditions.
Each test is performed separately for each phase. As long as the trip time falls between bands on the time-current curves, the circuit breaker is considered to be in working condition.
Note: the ground fault sensor must be disabled to test long, short, and instantaneous trips.
User guides and documents
FAQ / Frequently Asked Questions
The output current of the unit is considerably affected by the strength of the source. At 480 V, the SPI can draw up to 800 amps (for a very short time during instantaneous tests). Adding 40 ft of cable will result in a 1 % voltage drop, which roughly corresponds to a similar loss in output capability.
El SPI4000 funcionará en un interruptor más pequeño, como uno de 100 amperios, y su salida es similar a la de un equipo de medida de alta corriente DDA. Puede esperar un rendimiento similar al de un DDA en un interruptor de 100 amperios. Sin embargo, es importante tener en cuenta que la salida del SPI4000 (o cualquier equipo de medida de alta corriente) se ve afectada por la caída de tensión experimentada durante el funcionamiento. La alimentación de los interruptores de 100 amperios suele transportarse por hilos de menor envergadura que la de los de 225 amperios. Durante la realización de medidas de alta corriente (como las instantáneas), el SPI puede consumir más de 800 amperios de corriente y la caída de tensión será más pronunciada en un servicio de 100 amperios que en otro de 225 amperios. Dado que esta corriente alta suele ser de duración muy corta, el interruptor de 100 amperios no se dispara. Sin embargo, la caída de tensión puede ser más significativa, lo que limita ligeramente la capacidad de salida total de la unidad.