About the product
- True portable outdoor-ready unit, IP 43
- Very easy to use 'turn and click' single rotary knob interface
- Surge/thump energy 2000 Joules
- DC testing up to 40 kV, surging/thumping up to 32 kV, burning up to 40 kV
- Pre-location methods: Inductive ARM with multishot, ICE, and DECAY
- Built-in safety circuits for earth connection monitoring (F-Ohm) and touch potential monitoring (F-Voltage)
- Full TDR control of all HV functions
The STX40 portable fault location system is the most powerful of its kind in the market. It is ideal for proof testing, analysing, pre-locating and pinpointing faults on extruded low voltage and medium voltage XLPE- and EPR-insulated cables. With its 40 kV DC source, and a potent high frequency burner, it is also highly effective on PILC cables.
The STX40 is fully automated with motorised HV switches controlled by either the rotary knob or the industry-grade colour touch screen.
Technical specifications
- Power source
- Mains
- Test type
- Portable cable fault location
Product documents
Software and firmware updates
STX Operating Firmware
STX Operating Firmware
latest version
For update packages that contain only one rpm file and therefore only require an update of the operating software, proceed as follows:
1. Copy the zip file to the main directory of a USB flash drive.
2. Unzip the zip file to obtain the rpm file in main directory of the USB flash drive.
3. Insert the USB flash drive into the USB port of the powered-off STX 40.
4. Turn on the STX 40.
Result: The new version of the operating software is automatically detected and installed at start-up.
Do not turn off STX 40 during the update.
MeggerBook
MeggerBook & MeggerBook Lite
MeggerBook & MeggerBook Lite Software
latest version
What’s new in version 3.5.2
What’s new:
- added support for Bifröst device; data analysis /-data processing
- added new diagram functions
- added possibility for curve shifting
Improved:
- improved the selection menu for the new TanDelta-standard
- improved interface for editing the cable plan
- improved cable assignment procedure
- Improved diagram legend
- Improved details view for Loop on Loop off measurements
Bugfixes:
- fixed some bugs in the design
- fixed some system interruptions related to working with the database
- fixed an error in calculating the I leak start/end values
- fixed interface errors by working with the map
- fixed problems with changing the color and type of insulation
- fixed interface errors in creating report templates
- fixed a computational error of the tutu parameter in TD record
- fixed various report-related bugs
Removed:
- the possibility of automatic updates has been removed
The setup file below is suitable for the installation of both MeggerBook (full version) and MeggerBook Lite (free limited version).
When started with after adding the electronic license key into the installed software, the software starts as MeggerBook full version which allows for easy and comprehensive data evaluation, data archiving, cable management and report creation. A personal quotation for a certain number of licenses can be requested here . The new electronic license key allows for 3 devices to have MeggerBook full version installed on them.
The dongle key licenses from older versions of MeggerBook are not supported with this newer version. Updated electronic license keys can be requested here for previous customers.
Without the required software license key the software starts as MeggerBook Lite which allows for seamless report creation and offers some of the features as the full version while limiting the data storage options as follows:
• Measurements, analyses and reports are not permanently stored in the database
• While cable import and storage are not limited, a maximum of 5 cables can be created using the cable editor of the Lite Edition
At this time, the software can handle the measurement and test data of the following Megger devices:
Test vans: Centrix, Centrix City, Compact City, R30, Variant
Test systems: VLF Sine Wave 45 / 62, VLF CR 40/60, TDS 40/60
TDRs: Teleflex VX(-P), Teleflex SX
Note for test systems VLF Sine Wave 45 and VLF Sine Wave 62:
Data of these test systems can only be imported into the software, if the test systems is equipped with firmware version 3.14 or higher. The latest firmware can be found here (VLF Sine Wave 45) and here (VLF Sine Wave 62).