TTRU1 handheld transformer turns ratiometer
Highly accurate in a wide temperature range, ensuring adaptability to diverse working conditions
0.05 % accuracy from -20 °C to 50 °C
Configurable vector lists for testing efficiency
Simplifies testing of frequently tested transformer configurations
Powered by a rechargeable battery for maximum portability and flexibility
USB-C charging for included NiMH batteries
Go/No Go open-circuit, short-circuit, and inductance tests for a prompt diagnosis
Quick pass/fail evaluation of primary and secondary windings
Short-circuit impedance measurements conveniently bundled with a ratiometer
Verification to nameplate values to ensure there are no signs of winding deformation
À propos du produit
The TTRU1 is the latest handheld transformer turns ratiometer from Megger. In addition to routine polarity validation and turns ratio tests, the TTRU1 can measure short-circuit impedance (leakage reactance) with the same one-time connection.
Guided by colour-coded leads, clamps, and customisable on-screen vectors that match the transformer nameplate under test, the easy-to-follow setup ensures the right result the first time.
Perform up to 1000 turns ratio tests on a single NiMH AA battery charge. When it’s time to recharge the batteries, connect to any standard USB wall charger, or connect to your PC. When connected to the PC, TTRU1-EXP results can be downloaded, and the user guide and data sheet can also be accessed.
FAQ / Foire aux questions
Les modèles ADV, PRO et EXP du TTRU1 peuvent enregistrer jusqu'à 10 couplages de transformateur définis par l'utilisateur avec des tensions d'enroulement identifiées par un ID personnalisé. Après avoir enregistré un couplage personnalisé, les types de transformateurs courants d'un système peuvent être rappelés facilement pour garantir une évaluation correcte des résultats.
Le TTRU1 excelle dans le test des transformateurs de distribution monophasés, mais peut également être utilisé pour tester des transformateurs de puissance. Le TTRU1 s'affranchit de l'imprécision des résultats de test associée à la tension de test grâce à une tension induite pouvant atteindre 250 V CA et à une technologie brevetée reposant sur la mesure élévatrice du rapport de transformation, qui lui permet de tester n'importe quelle taille de transformateur.
Tous les modèles de TTRU1 enregistrent automatiquement les résultats lorsqu'un test est terminé. Les résultats peuvent être exportés au format Excel et PDF à l'aide d'une clé USB. Pour les clients ayant besoin d'un exemplaire papier des résultats, une imprimante USB est disponible en option. Les modèles ADV, PRO et EXP fournissent un fichier d'exportation supplémentaire à importer dans PowerDB (bientôt disponible). Les modèles PRO et EXP permettent de naviguer à l'écran entre les différents résultats pour une consultation sur site.
Le TTRU1 est initialement conçu pour tester les transformateurs monophasés, mais il peut également être utilisé pour les transformateurs triphasés. Les modèles ADV, PRO et EXP vous guideront tout au long des tests des transformateurs triphasés en affichant à l'écran les schémas de connexion, afin de configurer les tests et d'évaluer les résultats en toute confiance.
Produits connexes
Dépannage
- Ensure batteries are installed.
- Ensure batteries have sufficient charge.
- If using Alkaline batteries, replace batteries.
- If using NiMH batteries, charge the TTRU1 using the included USB-C to USB-A or USB-C to USB-C cable.
- If charging does not work, replace the NiMH batteries.
- Turn the selection knob to “INFO”.
- Run a self-check and follow the direction on screen.
- Turn the selection knob to “TTR”.
- Connect leads H1 to X1, H2 to X2, and run a 1:1 test using the 1ph0 diagram.
- Connect to a TRS1 to perform calibration verification.
- Check that the USB file structure is FAT32 or exFAT.
- Insert USB drive into the TTRU1, turn the selection knob to “INFO” and select “EXPORT DATA”.
Interprétation des résultats de test
The ratio is the measured transformer turns ratio (TTR), calculated using both the voltage applied to one side of the transformer and the induced voltage measured on the other. Calculated TTR is determined from the transformer's nameplate voltages and the k factor, if necessary, as given in the table below. With the measured TTR in hand, a percentage deviation from the calculated TTR can be computed, either manually or automatically by the TTRU3. As per IEEE, the percentage deviation between measured and calculated TTR should be within a ±0.5 % tolerance.
Transformer configurations / vector groups | TVR recalculation factor (k), TVR=k*TNR |
---|---|
Dd | 1 |
Dy | √3 |
Dyn | √3 |
Dz | 1.5 |
Dzn | 1.5 |
Yd | √3/2 |
YNd | 1/√3 |
Yy | 1 |
YNy | 1 |
Yyn | 1 |
YNyn | 1 |
Yz | √3/2 |
YNz | √3/2 |
Yzn | √3 |
YNzn | √3 |
Zd | 1 |
ZNd | 2/3 |
Zy | √3/2 |
ZNy | 1/√3 |
Zyn | 1 |
ZNyn | 1 |
IEEE documents cases of transformers that have a load tap changer in their low voltage side with an overall low number of turns that will cause some of the tap steps not having the same number of turns as others. Thus, the variation per tap is not uniform and might be outside the 0.5 % tolerance of deviation from nameplate values. In these cases, there are two criteria used to evaluate the results. First, the measured TTR at both extreme ends of the tap changer (highest and lowest) should be within the 0.5 % tolerance from the calculated TTR. Second, for any given tap, all three phases of the transformer should have the same voltage ratios.
Go/No Go testing provides open circuit, short circuit, and inductance verification of the transformer under test. When an open or short circuit is detected, the TTRU1 will indicate which winding has an issue.
Short-circuit impedance values should be within 3 % of nameplate values. The TTRU1 allows the operator to input nameplate KVA and Z % and will display the measured percent error on screen.
Manuels d'utilisation et documents
Mises à jour du logiciel et du micrologiciel
FAQ / Foire aux questions
Le TTRU1 utilise le mode « Step-up » lorsque les tensions de test sont supérieures à 50 V, en appliquant une tension à l’enroulement secondaire/tertiaire et en induisant et mesurant la tension sur l’enroulement primaire. Quel que soit le mode de test actif, l'instrument effectue d'abord un test de sécurité et de connexion à basse tension (moins de 1 V). Le mode « Auto test » utilise les résultats de ce test pour vérifier que le test peut passer en mode « Step-up ».
Vous devez effectuer un contrôle complet des performances et de l'étalonnage de votre TTRU1 au moins une fois par an. Cela permet de s'assurer que le TTRU1 fonctionne correctement sur toute la plage de mesure. L’étalonnage du TTRU1 peut être effectué par tous à l’aide de l’appareil TRS1 (Transformer Ratio Standard) de Megger disponible en option. Cet appareil d’étalonnage de transformateurs haute précision peut simuler des rapports de transformation en mode « Step-down » (abaisseur) (pour des ratiomètres classiques et le TTRU1) et en mode « Step-up » (élévateur) (pour les ratiomètres à manivelle Biddle et le TTRU1). Megger procède à un étalonnage de chaque unité TTRU1 neuve ou réparée avant de l'envoyer au client.
La maintenance ne doit être assurée que par du personnel qualifié et familiarisé avec les risques liés à l'utilisation d'un équipement de test haute tension. Il est impératif de bien lire et comprendre les sections 1, 2, 3, 4 et 5 du Manuel d’utilisation avant toute intervention. Le TTRU1 ne nécessite qu'une inspection périodique. Vérifiez que tous les éléments matériels sont en bon état. Le TTRU1 peut être nettoyé régulièrement. Pour ce faire, veillez à ce que l’eau ne pénètre pas dans les trous du panneau. Un produit nettoyant ménager pour tout usage, sous forme de spray, peut être utilisé pour nettoyer le panneau. Lustrez avec un chiffon doux et sec. Nettoyez les câbles et les prises du panneau à l'aide d'un chiffon propre imbibé d'alcool isopropylique ou dénaturé.
L'entretien ou la réparation de cet équipement ne doit être effectué que par du personnel qualifié conscient des dangers électriques et des précautions à prendre pour éviter des blessures. Megger propose un service complet de réparation et d'étalonnage et recommande à ses clients de profiter de ce service pour l'entretien de routine ou en cas de dysfonctionnement de l'équipement. Si un entretien est nécessaire, contactez votre représentant Megger pour obtenir un numéro d'autorisation de retour de produit (RA) et les instructions d'expédition. Les équipements doivent nous être envoyés en port prépayé et assuré, à l'attention du Département Réparation de Megger. Veuillez indiquer toutes les informations pertinentes, y compris la référence du catalogue, le numéro de série et les symptômes.